Life safety learning hub
Life Safety Systems
Emergency lighting to BS 5266, evacuation alert systems under BS 8629, sprinkler and suppression systems to BS EN 12845, and dry/wet risers to BS 9990 — the life safety infrastructure that keeps buildings evacuable.
In short
Life safety systems keep people alive during a fire long enough to evacuate or be rescued. Emergency lighting needs monthly function tests and annual 3-hour duration tests. Dry risers need annual wet pressure testing. Evacuation alert systems are mandatory in new high-rise residential over 18 metres.
Legal snapshot
What the law says
- BS 5266-1:2016
- Emergency lighting design, installation and testing — monthly function test, annual full-duration test.
- BS 9990:2015
- Non-automatic fire-fighting systems in buildings — dry and wet risers, annual pressure test.
- BS 8629:2019
- Evacuation alert systems for use by Fire and Rescue Services in blocks of flats.
- BS EN 12845
- Fixed fire-fighting systems — sprinkler systems, design and maintenance.
On the ground
Common problems & fixes
- Emergency lighting log book gapsFix, Contract a BAFE-registered maintainer for monthly and annual testing, with a digital log accessible to the RP.
- Dry riser inlet valve seizedFix, Annual wet pressure test with a certified specialist — a failure blocks fire service intervention.
- Sprinkler heads painted over during refurbishmentFix, LPS 1048-approved contractor to replace heads and recommission the zone.
- New high-rise handed over without an EASFix, Commission a BS 8629 evacuation alert system before occupancy — required for new residential over 18 metres.
Emergency Lighting Testing to BS 5266: Duty Holder Guide
Monthly function tests, annual 3-hour duration tests, log book requirements and remediation timelines for emergency lighting under BS 5266-1:2016.
Read the full guideAll life safety guides
1 guideFAQ
Frequently asked
- How often must emergency lighting be tested?
- BS 5266 requires a monthly function test (short) and an annual full-duration test — typically three hours for maintained systems.
- Are sprinklers mandatory in high-rise flats?
- For new residential buildings in England over 11 metres, Approved Document B requires automatic sprinklers throughout.
- What is an evacuation alert system?
- A BS 8629 system installed for use by the Fire and Rescue Service to alert residents floor by floor during a fire — mandatory in new-build residential over 18 metres.
Need life safety handled now?
Submit a brief and the desk will match you with three verified specialists in 48 hours. Free for building owners and managers, accreditation-verified, no pressure to appoint.
Submit a brief