HVAC learning hub
HVAC
Heating, ventilation and air conditioning compliance: TM44 air-con inspections, F-Gas record keeping, TR/19 ventilation hygiene, boiler and plant maintenance under UK regulation.
In short
Air conditioning systems over 12 kW require a TM44 inspection every 5 years, lodged on the Non-Domestic MEES register. F-Gas equipment needs leak checks between 3 and 12 months depending on charge size. Grease extract ductwork should be cleaned to TR/19 based on usage.
Legal snapshot
What the law says
- Energy Performance of Buildings Regulations 2012
- TM44 air conditioning inspections every 5 years for systems >12 kW effective rated output.
- F-Gas Regulation (EU) 517/2014 (retained)
- Leak checks, record keeping and certified engineers for refrigerant charges above CO2-equivalent thresholds.
- Workplace (Health, Safety and Welfare) Regulations 1992
- Regulation 6 — enclosed workplaces must be ventilated by fresh or purified air.
- BESA TR/19 (Guide to Good Practice)
- Internal cleanliness of ventilation systems, including kitchen grease extract.
On the ground
Common problems & fixes
- No TM44 report on fileFix, Commission a Level 3 or 4 TM44 assessor; report lodged within 3 months of inspection.
- F-Gas logbook not maintainedFix, REFCOM-registered contractor for leak checks; digital logbook accessible to the Environment Agency on request.
- Grease extract not cleaned — insurer non-complianceFix, TR/19-certified cleaner with post-clean deposit thickness test and photographic evidence.
- Fresh air rates below CIBSE Guide AFix, Airflow survey and commissioning — often solved by damper rebalance rather than plant replacement.
TM44 Air Conditioning Inspections: Duty Holder Guide
Who needs a TM44, how often, what a Level 3 or 4 assessor covers, the MEES register, and how to close energy performance recommendations.
Read the full guideAll hvac guides
1 guideFAQ
Frequently asked
- How often is a TM44 inspection?
- Every 5 years for air conditioning systems with an effective rated output over 12 kW, including packaged split systems where the aggregate exceeds 12 kW.
- Who needs F-Gas certification?
- Any person installing, servicing, maintaining, repairing or decommissioning stationary refrigeration, air conditioning and heat pump equipment containing fluorinated greenhouse gases.
- How often should kitchen extract be cleaned?
- TR/19 sets frequency by usage: heavy use (12+ hours/day) quarterly, moderate use (6–12 hours) every 6 months, light use annually.
Need hvac handled now?
Submit a brief and the desk will match you with three verified specialists in 48 hours. Free for building owners and managers, accreditation-verified, no pressure to appoint.