School Compliance Checklist: Statutory Duties for Estates

School compliance checklist for England: who the employer is, DfE GEMS duties, fire, asbestos, RAAC, legionella, electrical, gas, lifts, playground checks.

Joe LewinJoe Lewin
PUBLISHED 3 SEP 2026UPDATED 3 SEP 202618 MIN READ
Watercolour illustration of a school hand bell and satchel
KEY TAKEAWAYS

A school's statutory compliance duties sit with its employer: the local authority for community and voluntary controlled schools, the governing body for foundation and voluntary aided schools, the academy trust for academies, and the proprietor for independent schools. The DfE Good Estate Management for Schools guidance lists the disciplines: fire, asbestos, legionella, electrical, gas, structural including RAAC, lifts, pressure systems and playground equipment, each with a regulation and frequency.

What the law requires

A school is a workplace under the Health and Safety at Work etc. Act 1974, a non-domestic premises under the Regulatory Reform (Fire Safety) Order 2005, a building with lifts, boilers, kitchens and water systems, and, for most of the estate, a building constructed before 2000 that may contain asbestos. Every one of those attracts a statutory regime. The Department for Education's Good Estate Management for Schools (GEMS) guidance, last updated in July 2026, sets out the disciplines the responsible body must manage, and states that where it says "you must", a statutory requirement applies.

This guide converts the GEMS list into a compliance matrix with the governing instrument and frequency for each discipline, and explains the two things schools get wrong most often: who the employer is, and the difference between a statutory interval and a recommended one. For the equivalent matrices for other building types, see our care home compliance checklist and our hotel compliance checklist.

Who is responsible

DfE guidance states that the employer, or the proprietor in an independent school, is accountable for the health and safety of staff and pupils. The employer varies by school type, and getting it wrong means the wrong organisation is signing the fire risk assessment and holding the asbestos register.

Who is the employer and duty holder, by school type

School typeEmployer and duty holderNotes
Community, community special, voluntary controlled, maintained nursery, pupil referral unitThe local authorityThe authority can direct the governing body and head on health and safety matters
Foundation, foundation special, voluntary aidedThe governing bodyOften relies on a local authority service level agreement for compliance, but the duty stays with the governors
Academy, free school, university technical collegeThe academy trustMulti-academy trusts hold the duty across every school; the Academy Trust Handbook (2025 edition current, 2026 edition effective 1 October 2026) requires trusts to manage their estates
Independent schoolThe proprietorIncludes the governing body or company that owns the school

The head teacher and site team manage compliance day to day, and GEMS expects a named estates lead. Enforcement sits with the fire and rescue authority for fire and, under Regulation 4 of the Health and Safety (Enforcing Authority) Regulations 1998, with HSE for premises occupied by a local authority. Our duty holder guide explains how these roles are recorded.

The compliance matrix

School statutory compliance matrix by discipline

DisciplineGoverning instrumentTaskFrequencyBasis
Fire risk assessmentFire Safety Order 2005, Art. 9; Home Office educational premises guideAssessment recorded in full; action planReview regularly and on change; annual review commonStatutory duty, interval by risk
Fire alarm, emergency lighting, extinguishers, fire doorsFire Safety Order Art. 17; BS 5839-1, BS 5266-1:2025, BS 5306-3, BS 8214Test and serviceAlarm weekly test and 6-monthly service; lighting monthly and annual 3-hour test; extinguishers annual; doors at least 6-monthlyStandard
AsbestosControl of Asbestos Regulations 2012, Reg. 4Management survey; register; management plan; re-inspection; contractor informationPlan reviewed regularly; re-inspection interval per plan, commonly annualStatutory duty
Structural, including RAACHSWA 1974; DfE RAAC identification guidanceConfirm RAAC presence with a surveyor or structural engineer; notify DfE; manage per engineer's adviceOn identification and per engineerStatutory duty, guidance on method
LegionellaHSWA 1974; COSHH 2002; ACOP L8; HSG274 Part 2Risk assessment; written scheme; monitoring; flushing after holidaysWeekly flushing of little-used outlets; monthly temperatures; quarterly showerheads; annual tank inspectionACOP
Fixed electrical installationElectricity at Work Regulations 1989, Reg. 4(2); BS 7671; IET GN3Periodic inspection, EICRMaximum 5 years recommended for educational establishmentsGuidance
Portable and movable equipmentElectricity at Work Regulations 1989; IET Code of Practice (5th edition); HSE INDG236User checks; formal visual inspection; combined testRisk-based; Class I earthed equipment 1 to 2 years in low-risk areas; shorter in science, DT and cateringGuidance
Gas installation, boilers, cateringGas Safety (Installation and Use) Regulations 1998Safety check and service by Gas Safe registered engineerAnnualStatutory duty
Pressure systems (boilers, autoclaves, compressors)Pressure Systems Safety Regulations 2000Written scheme; examinationPer written schemeStatutory
Lifts, platform lifts, hoistsLOLER 1998, Reg. 9; PUWER 1998, Reg. 5Thorough examination; maintenance6 months for equipment lifting persons; 12 months goods onlyStatutory
Playground and fixed play equipmentHSWA 1974; BS EN 1176Routine visual, operational and annual main inspectionRoutine weekly to monthly; annual main inspection by competent personStandard
Swimming poolsHSWA 1974; HSG179Pool safety operating procedure; water treatmentPer procedureGuidance
Kitchen extractFire Safety Order Art. 17; BESA TR19 GreaseGrease removal and verification reportBy cooking hours; school kitchens typically moderate use, 6-monthlyIndustry specification, insurer condition
Air conditioning over 12 kWEnergy Performance of Buildings (England and Wales) Regulations 2012TM44 inspectionEvery 5 yearsStatutory
Lightning protectionBS EN 62305Inspection and testAnnual recommendedStandard
Glazing, working at height, COSHH, radonHSWA 1974; Work at Height Regulations 2005; COSHH 2002Risk assessment and controlsPer assessmentStatutory duty

Fire safety in more depth

The Home Office guide Fire safety risk assessment: educational premises, published under Article 50 of the Fire Safety Order and last updated in 2023, is the reference document. Schools have three features the assessor must address: large numbers of children who need supervised evacuation, specialist rooms with higher ignition risk (science laboratories, design technology workshops, kitchens), and out-of-hours lettings that change the occupancy profile. Since 1 October 2023 the assessment must be recorded in full and the assessor's name recorded, under Section 156 of the Building Safety Act 2022. Building Bulletin 100, the DfE design guide for fire safety in schools, governs new buildings and major refurbishments; the department has consulted on a revision, and the current status of that revision should be checked before specifying new works. Our fire risk assessment requirements guide covers who must do the assessment and how to judge competence, and our fire door inspection guide covers the doors that protect corridors and stairs.

Asbestos and RAAC

Most of the school estate predates 2000, and Regulation 4 of the Control of Asbestos Regulations 2012 places the duty to manage on the person with maintenance and repair obligations. The DfE guidance Managing asbestos in your school or college confirms that the legal duties are set by HSE and defers to HSE for their content. The practical regime is a management survey, an asbestos register, a written management plan, periodic re-inspection of known materials, and provision of the register to every contractor before work starts. A refurbishment and demolition survey is required before intrusive work.

RAAC is a structural duty rather than a compliance inspection. The DfE identification guidance, updated in July 2026, asks responsible bodies to appoint a building surveyor or structural engineer to confirm whether RAAC is present, to notify the department through its structural issues form, and to manage the material on the engineer's advice. The department has committed to funding removal of RAAC in English schools and colleges through grants or the school rebuilding programme.

Water hygiene in more depth

Schools have a legionella profile shaped by the calendar. Outlets stand unused for six weeks in summer and two weeks at Christmas and Easter, so the written scheme must require flushing before reoccupation and weekly flushing of any outlet unused in term time. Science laboratory taps, changing room showers and sports hall outlets are the common little-used outlets. Our legionella risk assessment guide covers the assessment and our water tank inspection guide covers the roof tanks found in many older school blocks.

Electrical in more depth

The fixed installation follows the five-year EICR interval recommended in IET Guidance Note 3 for educational establishments. Portable equipment follows the IET Code of Practice for In-service Inspection and Testing, fifth edition, which sets intervals by risk rather than by a fixed table, and HSE's INDG236 gives suggested initial intervals for low-risk environments. Classrooms and offices are low risk; science, design technology, food technology and site maintenance workshops are not, and their equipment warrants shorter intervals recorded in the equipment register. Our PAT testing requirements guide explains the regime.

What good evidence looks like

GEMS expects the responsible body to hold a compliance record it can produce on request. For each school that means: the current fire risk assessment and action plan; alarm, lighting, extinguisher and door records; the asbestos register and management plan with the last re-inspection; the RAAC position with the engineer's report; the legionella risk assessment, written scheme and logs including holiday flushing; the EICR and remedial certificates; the PAT register; gas safety records; pressure system written schemes and reports; LOLER reports; playground inspection reports; and the TM44 report where relevant. Each entry should show the date, the contractor, the contractor's competence evidence and the next due date. Multi-academy trusts should hold this per school in one system so the trust board can see the estate at a glance.

Common failures and enforcement consequences

  • Wrong duty holder. A governing body assuming the local authority still holds the duty after conversion to an academy.
  • Holiday stagnation. No flushing record for the first week of term.
  • Asbestos register not shown to contractors. The most common asbestos breach in schools.
  • Specialist rooms treated as low risk for PAT. Laboratory and workshop equipment on an office interval.
  • Fire risk assessment not reviewed after a new block or a modular classroom.
  • Lettings. Evening and weekend hirers with no fire procedure and no trained person on site.

The fire and rescue authority enforces the Fire Safety Order through enforcement and prohibition notices, and HSE enforces health and safety law on local authority premises. Our 28-day enforcement notice guide sets out the response if a notice arrives.

Scotland, Wales and Northern Ireland

Health and safety law applies across Great Britain with Northern Ireland parallels. Fire safety law differs: the Fire Safety Order in Wales; the Fire (Scotland) Act 2005 and Fire Safety (Scotland) Regulations 2006 in Scotland; the Fire and Rescue Services (Northern Ireland) Order 2006 in Northern Ireland. The DfE guidance cited here applies to England; the devolved education departments publish their own estates guidance.

Working with TICDesk

TICDesk is a UK procurement desk for testing, inspection and compliance work. Tell us the number of schools, the disciplines that are due and your deadline, and we introduce up to three vetted providers per discipline, typically within 48 hours. The service is free to the client; TICDesk earns a success fee from the contractor. Visit our desks for fire safety, water hygiene, electrical, lifts and HVAC, or open a brief.

Frequently asked

Who is legally responsible for health and safety compliance in a school?

The employer. Department for Education guidance states that the employer, or the proprietor for independent schools, is accountable for the health and safety of staff and pupils. For community, voluntary controlled, community special and maintained nursery schools and pupil referral units the employer is the local authority. For foundation and voluntary aided schools it is the governing body. For academies and free schools it is the academy trust. The head teacher manages day to day.

What compliance checks does a school need?

The DfE Good Estate Management for Schools guidance groups them as asbestos, fire safety, water and legionella, electrical fixed installations and portable appliances, gas, heating systems, structural stability including RAAC, working at height, glazing, air quality and ventilation, lifts and lifting equipment, playground equipment, swimming pools, kitchens, pressure systems, hazardous substances, lightning protection, accessibility and radon. Each has its own regulation and frequency, set out in the table in this guide.

Does a school need a fire risk assessment?

Yes. The Regulatory Reform (Fire Safety) Order 2005 applies to all schools in England and Wales, and the Home Office guide Fire safety risk assessment: educational premises is the published reference. Since 1 October 2023 the assessment must be recorded in full under Section 156 of the Building Safety Act 2022. It should be reviewed after any building work, change of use or fire, and the head teacher and governors should see the action plan.

What are the asbestos duties for schools?

Regulation 4 of the Control of Asbestos Regulations 2012 places a duty to manage asbestos in non-domestic premises on the person with maintenance and repair obligations, which in a school is the employer. The DfE guidance Managing asbestos in your school or college confirms the legal duties are set by HSE. In practice this means a management survey, an asbestos register, a written management plan, re-inspection of known materials and information to contractors before any work.

What is the RAAC duty for schools?

Reinforced autoclaved aerated concrete is a lightweight concrete used in roofs and floors, mainly between the 1950s and 1990s. The DfE identification guidance asks responsible bodies to appoint a building surveyor or structural engineer to confirm whether RAAC is present and to inform the department immediately through its structural issues form. The DfE has committed to funding removal of RAAC in English schools and colleges through grants or the school rebuilding programme.

How often does a school need an EICR and PAT testing?

IET Guidance Note 3 recommends a maximum five-year interval between periodic inspections of the fixed installation for educational establishments, subject to the previous report. Portable appliance testing has no statutory interval; HSE guidance INDG236 gives suggested initial intervals by equipment class, with Class I earthed equipment tested every one to two years in low-risk environments. Science, design technology and catering rooms are higher-risk environments and warrant shorter intervals set by risk assessment.

Does Ofsted inspect statutory compliance?

Ofsted inspects the quality of education, behaviour, personal development, leadership and safeguarding. It is not the enforcing authority for fire or health and safety law; the fire and rescue authority enforces the Fire Safety Order and HSE enforces health and safety on school premises where the local authority is the employer. Inspectors will however ask how leaders assure themselves that the premises are safe, so the compliance file should be available on the day.